UDCPR 2020 / Chapter 10, City specific regulations

10.2.12 Podium

UDCPR 2020 as amended to 30.01.2025

Podium for parking alongwith ramp may be permitted with side and rear marginal distance of 1.5 m. from plot boundary, subject to following conditions :-

a) Top of the Podium shall be accessible for Fire Engine by 7.5 m. Ramp with gradient 1 : 10.

b) Structural Stability Certificate regarding such Podium and Ramp shall be submitted with respect to stand Fire Engine over it & sustain load of Fire Engine.

c) Minimum 6.0 m. marginal distances with required turning circle over the Podium shall be

provided for manoeuvring of Fire Engine.

Provided that, if the podium is not accessible for Fire Engine then 6.0 m. marginal open space shall be provided all around the building excluding front margin. Turning circle shall not be less than 9.0 m. The refuge area in such cases shall be facing front road and shall be connected to Fire Tower as per Clause 2.24 of Part - 4 of NBC 2016.

d) Provisions mentioned in Regulation No.9.13 shall be applicable except (ii).