UDCPR 2020 / Chapter 6, General building requirements - setback, marginal distance, height and permissible FSI
6.1.2 Other buildings like Public / Semi-Public, Educational, Medical, Institutional, Commercial,
UDCPR 2020 as amended to 30.01.2025
Mercantile, etc.
(a) Floor Space Index - The FSI permissible for these buildings shall be as per Regulation No.6.1.1.
(b) Marginal Distances - For these buildings marginal distances shall be 3.0 m. on all sides including front up to 24.0 m. height.
Provided that for building more than 24.0 m. height, regulations of non-congested area shall apply.
Provided further that, for buildings like cinema theatres, multiplex, assembly buildings, shopping malls etc., regulations for outside congested area, except FSI, shall apply.