9.4.3 Other requirements of bath room and water closet
UDCPR 2020 as amended to 30.01.2025
Every bathroom or water-closet shall –
i) be so situated that it derives ventilation from ventilation shaft or external air;
ii) have a window or ventilator, opening to a shaft or open space, of area not less than 0.3 sq.m. with side not less than 0.3 m.;
iii) all the sewerage outlets shall be connected to the sewerage system. Where no such systems exist, a septic tank shall be provided within the plot conforming to the requirements of Regulation No.9.25.