UDCPR 2020 / Chapter 9, Requirements of part of building
Table 9-A Height of Habitable Rooms (9.2.2)
UDCPR 2020 as amended to 30.01.2025
Table No.9-A
Sr. Occupancy Minimum Height Maximum Height
No. (m.) (m.)
(1) (2) (3) (4)
1 Flat Roof -
a) Any habitable room 2.75 4.5
a1) Habitable room in EWS / LIG Housing. 2.75 4.2
b) Air-conditioned habitable room 2.4 4.5
c) Assembly Halls, Residential Hotels of 3 3.0 6.00 or higher
star category and above, Institutional, (2.40 m. in case according to the
Educational, Industrial, Hazardous or storage of Air requirement of
occupancies, Departmental Stores, Malls, IT conditioned occupancy.
Buildings, Office Buildings, Exhibition room)
Centre, Convention Hall, Theatre, Film
Studio, Entrance Halls and Lobbies to these
buildings.
d) Shops 3.00 4.5
2 Pitched roof-
a) Any habitable room 2.75 (average 4.5 (average with
with 2.0 m. at the 3.2 m. at the lowest
lowest point) point)
b) Habitable room in EWS / LIG Housing. 2.6 (average with 4.2 (average with
2.0 m. at the 3.2 m. at the lowest
lowest point) point)
Provided that the minimum head-way under any beam shall be 2.4 m.
Provided further that height more than that specified above, if required for particular occupancy,
shall not be counted towards calculation of FSI.
To see how Table 9-A and the rest of UDCPR apply to a particular plot, with the clause behind every figure, open Citiwise.
UDCPR 2020, Table 9-A, as amended to 30.01.2025. https://citiwise.in/udcpr/table-9-a
Source
These words are UDCPR 2020 as the Directorate of Town Planning, Government of Maharashtra, publishes it in its consolidated text, as amended to 30.01.2025 with earlier provisions and corrections. Table 9-A is printed on pages 153 to 154 of that text. Read the official text (PDF).
The notification of the Urban Development Department, Government of Maharashtra, is the authoritative text.