UDCPR 2020 / Chapter 9, Requirements of part of building
Table 9-C Ventilation Shaft
UDCPR 2020 as amended to 30.01.2025
Table No.9-C - Ventilation Shaft
Sr. Height of Cross-section of Ventilation Minimum one dimension of
No. Buildings in m. shaft in Sq.m. the shaft in m.
(1) (2) (3) (4)
1 Upto10 1.2 0.9
2 Upto12 2.4 1.2
3 Upto 18 4.0 1.5
4 Upto 24 5.4 1.8
5 Upto30 8.0 2.4
6 Above 30 9.0 3.0
Note :-
a) For buildings above 30.0 m., mechanical ventilation system shall be installed besides the
provisions of minimum ventilation shaft.
b) For fully air-conditioned residential / other buildings, the ventilation shaft need not be
insisted upon, provided the air-conditioning system works in an uninterrupted manner, also
provided; there is an alternative source of power supply.