UDCPR 2020 / Chapter 9, Requirements of part of building
9.28.4 Arrangement of Exits
UDCPR 2020 as amended to 30.01.2025
Exits shall be so located that the travel distance on the floor shall not exceed as given below :-
Table No.9-D Type of Building Travel Distance
Residential, Educational, institutional and 22.5 m.
Hazardous occupancies Assembly, business, mercantile, Industrial and 30.0 m. Storage Occupancies.
Whenever more than one exit is required for a floor of a building, exits shall be placed at remote from each other as possible. All the exits shall be accessible from the entire floor area at all floor levels.
(1)
Note – For the buildings where sprinkler system has been provided in entire building for fire fighting, the travel distance may be increased by 50% of the value specified in above table.
Tables under this regulation: Table 9-D.