UDCPR 2020 / Chapter 9, Requirements of part of building
9.28.6 Capacity of Exits
UDCPR 2020 as amended to 30.01.2025
1) The unit of exit width use to measure the capacity of any exit should be 50 cm. A clear width of 25 cm. should be counted as additional half unit. Clear width less than 25 cm. should not be computed for exit width.
2) Occupants per unit exit width shall be in accordance with Table No.9-F Table No.9-F Sr. Number of Occupants Group of Occupancy
No. Stairways Ramps Doors
(1) (2) (3) (4) (5)
1 Residential 25 50 75
2 Educational 25 50 75
3 Institutional 25 50 75
4 Assembly 40 50 60
5 Business 50 60 75
6 Mercantile 50 60 75
7 Industrial 50 60 75
8 Storage 50 60 75
9 Hazardous 25 30 40Tables under this regulation: Table 9-F.