UDCPR 2020 / Chapter 12, Structural safety, water supply, drainage and sanitary requirements, outdoor display and other services

Table 12-A Per Capita Water Requirements for Various Occupancies / Uses

UDCPR 2020 as amended to 30.01.2025

Table No.12-A
                                           Per Capita Water Requirements for Various Occupancies / Uses
                  Sr.                                    Type of Occupancy                          Consumption per head
                  No.                                                                                 per day (in litres)
                   1                                                 2                                       3
                   1      Residential
                          (a) in living units                                                               135
                          (b) Hotels with lodging accommodation (per bed)                                   180

       (1)
             Substituted vide Corrigendum / Addendum No.CR.121/21, dt.02nd December, 2021

  1                                    2                                            3
  2    Educational
       (a) Day Schools                                                              45
       (b) Boarding Schools                                                        135
  3    Institutional (Medical Hospitals)
       (a) No. of beds not exceeding 100                                           340
       (b) No. of beds exceeding 100                                               450
       (c) Medical quarters and hostels                                            135
  4    Assembly :- Cinema theatres, auditorium etc. (per seat of                    15
       accommodation)
  5    Government and Semi-public business                                          45
  6    Mercantile (Commercial)
       (a) Restaurants (per seat)                                                   70
       (b) Other business buildings                                                 45
  7    Industrial
       (a) Factories where bathrooms are to be provided                             45
       (b) Factories where no bath-rooms are required to be                         30
       provided
  8    Storage (including warehousing)                                              30
  9    Hazardous                                                                    30
 10    Intermediate / Stations (excluding mail and express stops)               45 (25) *
 11    Junction Stations                                                        70 (45) *
 12    Terminal / Stations                                                          45
 13    International and domestic Airports                                          70
* - The value in parenthesis is for stations where bathing facilities are not provided.
Note : The number of persons for Sr.No.(10) to (13) shall be determined by the average
number of passengers, handled by the station daily; due consideration may be given to the
staff and workers likely to use the facilities.