UDCPR 2020 / Chapter 12, Structural safety, water supply, drainage and sanitary requirements, outdoor display and other services
Table 12-B Flushing storage capacities
UDCPR 2020 as amended to 30.01.2025
Table No.12-B
FLUSHING STORAGE CAPACITIES
Sr. Classification of building Storage capacity.
No.
(1) (2) (3)
1 For tenements having common 900 litres net per w.c. seat.
convenience
2 For residential premises other than 270 litres net for one w.c. seat and 180
tenements having common convenience litres for each additional seat in the same
flat.
3 For Factories and Workshops 900 litres per w.c. seat and 180 litres per
urinal seat.
4 For cinemas, public assembly halls, etc. 900 litres per w.c. seat and 350 litres per
urinal seat.